FAIL FREEZE POSITIONER : SS5

FAIL FREEZE POSITIONER, Perfect combination with reliable fail freeze function and smart performance with innovative durable coil drive

Features

 

- “Fail Freeze” function to help the valve stay at the last position on the loss of the electrical power supply
- Easy and quick auto-calibration 
- Detecting RA (reverse acting) or DA (direct acting) automatically regardless of wrong air connections
- Available to use for single or double acting without any special adjustments 
- Compact design allowing to be installed on small actuators
- Providing error messages against performance failures
- Possible to test the actuator with any fixed signal under a test mode
- Programmable characteristic curve with 17 points
- Wide operating temperature range -30 ~ +80℃
- Improved control of high-friction globe and ball valves by eliminating an overshoot and a hunting
- Low air consumption
- Providing a mounting bracket to meet IEC 60534-6-1 for linear valves
- Supporting a NAMUR mounting pattern VDI/VDE 3845 (IEC 60534-6-2) and providing a multi-size mounting bracket for rotary valves

 

Option

- Output position transmitter (4 - 20 mA)
- 2 x alarm limit or micro switch (SPDT)
- Explosion proof type (Exia IIC T6) (in progres)
- HART communication
- Profibus PA communication(pending)
- Fieldbus FF communication(pending)

 

Specifications

 

Input Signal

4 - 20 mA @ 24 VDC

Min. / Max. Current

3.6 mA / 50mA

Voltage Drop (Resistance)
Without Hart : 8.7 VDC (435Ω @ 20mA)
With Hart : 9.4 VDC (470Ω @ 20mA)

Stroke / Angle

Linear type : 8 - 130mm *
Rotary type : 25 - 120°

Air Supply Pressure

1.4 - 7.0 bar (20 - 100 psi)

Output Pressure Range

0 - 100% of supply air pressure

Air Capacity

80 ℓ/min = 4.8 Nm3/h = 2.8 scfm (Sup = 1.4 bar)
233 ℓ/min = 14 Nm3/h = 8.2 scfm (Sup = 6 bar)

Air Consumption

2.8 ℓ/min = 0.17 Nm3/h = 0.1 scfm (Sup = 1.4 ~ 6 bar)
Performance Characteristic

Linearity  <  ±0.3% F.S
Sensitivity  <   0.2% F.S
Hysteresis  <   0.2% F.S
        Repeatability  <   0.2% F.S          

LCD Indication

4-digit LCD indicator

Adjustable Speed

1 - 1000 ( lowest 1, highest 1000 )

Scan Time

2ms

Fail freeze level
Input signal < 3mA

Fail freeze drift rate

+2% setpoint / hour at constant temp

Shut-off Value
Range 0 - 10% of position signal

Valve Action

Direct action(DA) / reverse action(RA)

Operating Temperature

-30 ~ +80℃ (-22 ~ +176℉) **
Pneumatic Connections

Rc 1/4 or 1/4 NPT

Electrical Connections

2 x G 1/2 or 1/2 NPT

Protection Class

IP66,  intrinsic safety (Exia IIC T6)

Body Material

Aluminum die-cast / powder-painted

Weight

2 kg

 

How to order

 

SS5 -
Actuator Operation
Protection Class
Feedback Lever
Pressure 
Gauges
Position 
Feedback
Communi-
cation
 
Connection
Threads
Mounting
Bracket
Feedback Pin
Guide Lever Set



 

Description

Code

Actuator Operation :
L : Linear type
R : Rotary type
Protection Class :  I : Intrinsic safety 
    (IECEx Ex ia IIC T6
     ATEX EEx ia IIC T6)
K : Intrinsic safety 
    (KTL Ex ia IIC T6)
W : Weatherproof to IP66
Feedback Lever : 

- Linear Type




- Rotary Type


A: Stroke (8 ~ 30mm)
B: Stroke (8 ~ 65mm)
C: Stroke (8 ~ 130mm)
D: Stroke (80 ~ 200mm)

F: Fork lever 
N: Namur shaft (direct mounting)
Gauge Block : N : None
1 : 6 bar (90psi)
2 : 10 bar (150psi)

Description

Code

Position Feedback :
N : None
O : Position transmitter
     (4 ~ 20mA output signal)
L : 2 x alarm limit
S : 2 x micro switch (SPDT)
M : O+L
Q : O+S
Communication : N : None
H : HART communication
P : Profibus PA communication
F : Fieldbus FF communication
Connection Threads
(pneumatic-electrical)
3 : Rc 1/4 or G1/2 (standard)
4 : NPT 1/4 or NPT 1/2
5 : Rc 1/4 or M20 x 1.5
Mounting bracket :



N : None
L : IEC 60534-6-1 (for SS5L)
R : VDI/VDE 3845
    (IEC 60534-6-2)(for SS5R)
Feedback Pin Guide
Lever Set:
(only for linear type SS5L)
0 : Not included
1 : Included

 

Cr. : http://www.power-genex.com/