| Power supply |
19V ÷ 50V DC; 16V ÷ 35V AC or 85 ÷ 260V AC/DC |
| Input |
9 universal inputs max.; 48 analogue inputs (0/4-20 mA or 0/1-5V or 0/2-10V) max.; 48 digital inputs max.; 24 thermocouple inputs max.; 12 RTD inputs max.; 12 counter/ flowmeter/ ratemeter inputs max.; 1 digital input 24V DC (available in standard, integrated with PS3 or PS4 power supply module) |
| Display |
3.5 inch graphic TFT, 16-bit colour, 320 x 240 pixels, with touchscreen |
| Measurement range |
depends on input |
| Power consumption |
typical 15 VA; max. 20 VA |
| Output |
8 analog (4-20 mA) max.; 16 relay (1A/250V) max.; 4 relay 5A/250V max. or 16 SSR outputs, sensor supply: 24 V DC ± 5% (200 mA max. for current inputs) |
| Communication interface |
standard: RS-485 (Modbus RTU), 1 x USB Host; ETU version: 1 or 2 x USB Host, 1 x Ethernet 10 MB; enhanced ACM version: 2 x RS-485, 1 x RS-485/232, 1 or 2 x USB Host, 1 x Ethernet 10 MB |
| Internal memory capacity |
internal 1,5 GB |
| Protection class |
IP 65 (front), available options: additional frame IP 65 for panel cut-out sealing, transparent door STD-99; version with front USB: IP 40 or IP 54 (when fitted with STD-99 transparent door) |
| Case material |
NORYL - GFN2S E1 |
| Available data recording speed |
from 0,1 s to 24 h with resolution 0,1 s |
| Operating temperature |
0°C ÷ +50°C |
| Storage temperature |
-10°C ÷ +70°C |
| Case |
panel mounting |
| Panel cut-out dimensions |
90,5 x 90,5 mm |
| Case dimensions |
96 x 96 x 100 mm |
| Software |
Free DAQ Manager software for multichannel controller can be downloaded directly from section „Download” |
| Installation depth |
min. 102 mm |